This table is for the Sineng SN50PT and SN60PT (SN series) three phase on-grid inverters and comes from Sineng's SN series user manual. Other Sineng models may use different numbers, so check your own manual.

Diagram

Sineng alarm groups

Grid

1, 4, 5, 6

Panels and earthing

7, 8, 9, 10, 39, 40, 41

Inverter

21, 23, 24, 25, 33

Sineng SN50PT and SN60PT alarms by where the problem usually is.

Sineng SN50PT and SN60PT alarm table

CodeWhat it meansTypical cause
1Grid voltage abnormalSupply voltage outside the allowed range
4Grid frequency abnormalUnstable supply
5No mainsLoad-shedding or AC side disconnected
6Phase sequence reversedAC output wiring order
7GFCI (leakage) faultLeakage to earth
8ISO (insulation) faultDC cable or panel insulation
9DCI faultDC on the AC output
10Neutral-earth voltage abnormalNeutral or earthing problem
21Equipment abnormalInternal
23High temperatureHot room or blocked airflow
24Firmware versions do not matchInternal boards on different versions
25Communication faultCommunication cable
33Bus overvoltageInternal or PV voltage high
39AFCI (arc) faultLoose or damaged panel connection
40PV overvoltageString voltage too high
41PV connected in reversePanel string polarity

Sineng safe owner checks

  • Note the alarm number, its name and the time.
  • During load-shedding, "No mains" is normal. It clears when the supply returns.
  • Check that nothing is blocking airflow around the inverter.
  • Check the app for how often the alarm repeats.

When to call an engineer

  • Alarms 6, 7, 8, 9, 10, 39, 40 or 41: these are wiring, earthing or panel side checks for an engineer only.
  • Alarms 21, 24 or 33 that return after a restart: usually a manufacturer case.
  • Grid voltage or frequency alarms that happen every day.